Supply Ability: 300 sets per month
Cylinder Volume: |
80L, 90L |
Capacity: |
14.25kg, 16.04kg |
Pattern Of Extinguishing: |
Enclosed Flooding |
Agent: |
IG100 (100% Pressurized Nitrogen) |
Working Prussure: |
15MPa |
Color: |
Red |
Cylinder Volume: |
80L, 90L |
Capacity: |
14.25kg, 16.04kg |
Pattern Of Extinguishing: |
Enclosed Flooding |
Agent: |
IG100 (100% Pressurized Nitrogen) |
Working Prussure: |
15MPa |
Color: |
Red |
Description
The IG100 nitrogen fire suppression system, also known as an inert gas system, is a type of fire protection system that utilizes nitrogen gas to suppress fires in enclosed spaces. Here's a description of the IG100 nitrogen fire suppression system:
It's important to consult with fire protection experts and adhere to local regulations and guidelines when designing, installing, and maintaining an IG100 nitrogen fire suppression system. Proper system design and professional installation are crucial to ensure the system's effectiveness in suppressing fires and protecting lives and property.
Parameters of Fire Suppression System
No. | Specification | Technical Parameter | |
1 | Working Pressure | 15Mpa | |
2 | Device Model | QMD15/80 | QMD15/90 |
3 | Capacity | 80Ltr | 90Ltr |
4 | Filling Capacity of Gas | 14.25kg | 16.04kg |
5 | Outside Diameter of Cylinder | Φ279mm | Φ325mm |
6 | Height of Cylinder | 1578+73mm | 1345+60mm |
7 | Spraying Time | ≤10s | |
8 | Max Filling Rate | 0.178kg/L | |
9 | Power | DC24V/1.6A | |
10 | Nitrogen Pressure of Driving Device | 6.0±1.0Mpa(20℃) | |
11 | Condition of Reserving Room for Container | temperature: 0~50℃ | |
12 | Max Working Pressure | 17.2Mpa | |
13 | Min Working Pressure | 13.6Mpa |
Application of Fire Suppression System
Fire suppression systems are designed to detect, contain, and extinguish fires in buildings, vehicles, and other enclosed spaces. Here are some common applications of fire suppression systems:
In general, fire suppression systems are crucial for preventing the disastrous impacts of fires on people and property. To make sure they'll work in an emergency, they should be installed and maintained by trained experts. To achieve the highest level of safety, fire suppression systems should be utilized in conjunction with fire preventive strategies including routine fire drills, smoke detectors, and fire extinguishers.
Advantages
The number of fire extinguishing agent cylinders may be reduced by 25% to 50% when compared to the typical 15MPa system.
The building's occupancy and usage rates have both increased, and the between-cylinder space has been successfully decreased.
Pipelines and pipe fittings can be more affordably priced with a continuous 6MPa low pressure release.
A distance of 200 meters may be covered by the transfer of 6 MPa continuous release pressure, which is more durable and efficient.
The impact on workers at construction sites, machinery, and building structures will only be reduced and safety will increase with the release of the complete system under low pressure.
Packages
We always place it into a wooden case after first packing it with polyfoam. At times, we will create a pallet for the goods in order to satisfy clients or meet safety requirements.
Mimic Diagram
Single/Multiple cylinder(s) for multiple zone
Single/Multiple cylinder(s) for one zone
After-Sale Service
• We have an efficient sales and after sales team to promise slove all client's question in time.
• We provide 8×6 hrs technical support and service.